488 Fieldbus control through a fieldbus adapter
Contents of the fieldbus Status word (ABB Drives profile)
The upper case boldface text refers to the states shown in the state diagram on
page
489
.
11
Ext ctrl loc
1
Select External Control Location EXT2. Effective if control
location is parameterized to be selected from fieldbus.
0
Select External Control Location EXT1. Effective if control
location is parameterized to be selected from fieldbus.
12
User bit 0
1
User configurable.
0
13
User bit 1
1
0
14
User bit 2
1
0
15
User bit 3
1
0
Bit
Name
Value State/Description
0
Ready to switch
ON
1
READY TO SWITCH ON
.
0
NOT READY TO SWITCH ON
.
1
Ready run
1
READY TO OPERATE
.
0
OFF1 ACTIVE
.
2
Ready ref
1
OPERATION ENABLED
.
0
OPERATION INHIBITED
. See also parameter
06.18
Start
inhibit status word
(page
126
).
3
Tripped
1
FAULT
.
0
No fault.
4
Off 2 inactive
1
OFF2 inactive.
0
OFF2 ACTIVE
.
5
Off 3 inactive
1
OFF3 inactive.
0
OFF3 ACTIVE
.
6
Switch-on
inhibited
1
SWITCH-ON INHIBITED
.
0
–
7
Warning
1
Warning active.
0
No warning active.
8
At setpoint
1
OPERATING
. Actual value equals reference = is within
tolerance limits (see parameters
46.21
…
46.23
).
0
Actual value differs from reference = is outside tolerance
limits.
9
Remote
1
Drive control location: REMOTE (EXT1 or EXT2).
0
Drive control location: LOCAL.
10
Above limit
-
See bit 10 of
06.17
Drive status word 2
.
11
User bit 0
-
See parameter
06.30
MSW bit 11 selection
.
12
User bit 1
-
See parameter
06.31
MSW bit 12 selection
.
13
User bit 2
-
See parameter
06.32
MSW bit 13 selection
.
14
User bit 3
-
See parameter
06.33
MSW bit 14 selection
.
15
Reserved
Bit
Name
Value State/Description
ACS380 FW.book Page 488 Friday, May 4, 2018 4:18 PM