58.26
EFB ref1 type
Selects the type and scaling of reference 1 received
through the embedded fieldbus interface.
The scaled reference is displayed by
03.09
EFB reference
1
.
Speed or
frequency
Speed or frequency
Type and scaling is chosen automatically according to the
currently active operation mode as follows.
0
Transparent
No scaling is applied.
1
General
Generic reference without a specific unit. Scaling: 1 = 100. 2
Torque
Torque reference. The scaling is defined by parameter
46.03
Torque scaling
.
3
Speed
Speed reference. The scaling is defined by parameter
46.01
Speed scaling
.
4
Frequency
Frequency reference. The scaling is defined by parameter
46.02
Frequency scaling
.
5
58.27
EFB ref2 type
Selects the type and scaling of reference 2 received
through the embedded fieldbus interface.
The scaled reference is displayed by
03.10
EFB reference
2
.
Speed or
frequency
58.28
EFB act1 type
Selects the type/source and scaling of actual value 1
transmitted to the fieldbus.network through the embedded
fieldbus interface.
Speed or
frequency
Speed or frequency
Type and scaling is chosen automatically according to the
currently active operation mode as follows:
0
Transparent
The value selected by parameter
58.31
EFB act1
transparent source
is sent as actual value 1. No scaling is
applied (the 16-bit scaling is 1 = 1 unit).
1
General
The value selected by parameter
58.31
EFB act1
transparent source
is sent as actual value 1 with a 16-bit
scaling of 100 =1 unit (ie. integer and two decimals).
2
Torque
01.10
Motor torque
is sent as actual value 1. Scaling is
defined by parameter
46.03
Torque scaling
.
3
Speed
01.01
Motor speed used
is sent as actual value 1. Scaling
is defined by parameter
46.01
Speed scaling
.
4
Frequency
01.06
Output frequency
is sent as actual value 1. Scaling
is defined by parameter
46.02
Frequency scaling
.
5
No.
Name/Value
Description
Default
FbEq 16
Operation mode
(see par.
19.01
)
Reference 1 type
Speed control
Speed
Torque control
Speed
Frequency control
Frequency
Operation mode
(see par.
19.01
)
Actual 1 type (source)
Scaling
Speed control
Speed
(
01.01
Motor speed used
)
46.01
Speed scaling
Torque control
Frequency control
Frequency
(
01.06
Output frequency
)
46.02
Frequency scaling