Parameters 263
In1-In2
Source 2 subtracted from source 1.
2
In1*In2
Source 1 multiplied by source 2.
3
In1/In2
Source 1 divided by source 2.
4
MIN(In1,In2)
Smaller of the two sources.
5
MAX(In1,In2)
Greater of the two sources.
6
AVE(In1,In2)
Average of the two sources.
7
sqrt(In1)
Square root of source 1.
8
sqrt(In1-In2)
Square root of (source 1 - source 2).
9
sqrt(In1+In2)
Square root of (source 1 + source 2).
10
sqrt(In1)+sqrt(In2)
Square root of source 1 + square root of source 2.
11
40.19
Set 1 internal setpoint
sel1
Selects together with
40.20
Set 1 internal setpoint sel2
the
internal setpoint out of the presets defined by parameters
40.21
…
40.23
.
Note:
Parameters
40.16
Set 1 setpoint 1 source
and
40.17
Set 1 setpoint 2 source
must be set to
Internal
setpoint
Not selected
.
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
10.02
DI delayed status
, bit 0).
2
DI2
Digital input DI2 (
10.02
DI delayed status
, bit 1).
3
DI3
Digital input DI3 (
10.02
DI delayed status
, bit 2).
4
DI4
Digital input DI4 (
10.02
DI delayed status
, bit 3).
5
DIO1
Digital input/output DIO1 (
11.02
DIO delayed status
, bit 0). 10
DIO2
Digital input/output DIO2 (
11.02
DIO delayed status
, bit 1). 11
Timed function 1
Bit 0 of
34.01 Timed functions status
.
18
Timed function 2
Bit 1 of
34.01 Combined timer status
.
19
Timed function 3
Bit 2 of
34.01
Combined timer status
.
20
Supervision 1
Bit 0 of
32.01 Supervision status
.
21
Supervision 2
Bit 1 of
32.01 Supervision status
.
22
Supervision 3
Bit 2 of
32.01 Supervision status
.
23
Other [bit]
Source selection (see
Terms and abbreviations
).
-
40.20
Set 1 internal setpoint
sel2
Selects together with
40.19
Set 1 internal setpoint sel1
the
internal setpoint used out of the three internal setpoints
defined by parameters
40.21
…
40.23
. See table at
40.19
Set 1 internal setpoint sel1
.
Not selected
Not selected
0.
0
No.
Name/Value
Description
Default
FbEq 16
Source defined by
par.
40.19
Source defined by
par.
40.20
Internal setpoint active
0
0
Setpoint source
1
0
1 (par.
40.21
)
0
1
2 (par.
40.22
)
1
1
3 (par.
40.23
)
ACS380 FW.book Page 263 Friday, May 4, 2018 4:18 PM