Parameters 269
40.45
Set 1 sleep boost time
Defines a boost time for the sleep boost step. See
parameter
40.46
Set 1 sleep boost step
.
0.0 s
0.0…3600.0 s
Sleep boost time.
1 = 1 s
40.46
Set 1 sleep boost step
When the drive is entering sleep mode, the process
setpoint is increased by this value for the time defined by
parameter
40.45
Set 1 sleep boost time
.
If active, sleep boost is aborted when the drive wakes up.
0.0 PID
customer
units
0.0…200000.0 PID
customer units
Sleep boost step.
1 = 1 PID
customer
unit
40.47
Set 1 wake-up
deviation
Defines the wake-up level as deviation between process
setpoint and feedback.
When the deviation exceeds the value of this parameter,
and remains there for the duration of the wake-up delay
(
40.48
Set 1 wake-up delay
), the drive wakes up.
See also parameter
40.31
Set 1 deviation inversion
.
0.00 PID
customer
units
-200000.00...200000.0
PID customer units
Wake-up level (as deviation between process setpoint
and feedback).
1 = 1 PID
customer
unit
40.48
Set 1 wake-up delay
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter
40.47
Set 1 wake-up
deviation
.
The delay timer starts when the deviation exceeds the
wake-up level (
40.47
Set 1 wake-up deviation
), and resets
if the deviation falls below the wake-up level.
0.50 s
0.00…60.00 s
Wake-up delay.
1 = 1 s
40.49
Set 1 tracking mode
Activates (or selects a source that activates) tracking
mode. In tracking mode, the value selected by parameter
40.50
Set 1 tracking ref selection
is substituted for the PID
controller output. See also section
Tracking
(page
84
).
1 = Tracking mode enabled
Not selected
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
10.02
DI delayed status
, bit 0).
2
DI2
Digital input DI2 (
10.02
DI delayed status
, bit 1).
3
DI3
Digital input DI3 (
10.02
DI delayed status
, bit 2).
4
DI4
Digital input DI4 (
10.02
DI delayed status
, bit 3).
5
DIO1
Digital input/output DIO1 (
11.02
DIO delayed status
, bit 0). 10
DIO2
Digital input/output DIO2 (
11.02
DIO delayed status
, bit 1) 11
Timed function 1
Bit 0 of
34.01 Timed functions status
.
18
Timed function 2
Bit 1 of
34.01 Timed functions status
.
19
Timed function 3
Bit 2 of
34.01 Timed functions status
.
20
Supervision 1
Bit 0 of
32.01 Supervision status
.
21
Supervision 2
Bit 1 of
32.01 Supervision status
.
22
Supervision 3
Bit 2 of
32.01 Supervision status
.
23
Supervision 4
Bit 3 of
32.01 Supervision status
24
Supervision 5
Bit 4 of
32.01 Supervision status
25
No.
Name/Value
Description
Default
FbEq 16