![ABB ACS380 Series Firmware Manual Download Page 354](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560354.webp)
354 Parameters
Differences in the default values between 50 Hz and 60 Hz
supply frequency settings
Parameter
95.20
HW options word 1
bit 0 changes the drive parameter default values
according to the supply frequency, 50 Hz or 60 Hz. The bit is set according to the
market before the drive is delivered.
If you need to change from 50 Hz to 60 Hz, or vice versa, change the value of the bit
and then do a complete reset to the drive (
96.06
Parameter restore
). After that you
have to reselect the macro to be used.
The table below shows the parameters whose default values depend on the supply
frequency setting. The supply frequency setting, with the type designation of the
drive, also affects group
99 Motor data
parameter values (not listed in the table).
No
Name
95.20 HW options word 1
bit 0
Supply frequency 60 Hz =
50 Hz
95.20 HW options word 1
bit 0
Supply frequency 60 Hz
=
60 Hz
11.45
Freq in 1 at scaled max
1500.000
1800.000
12.20
AI1 scaled at AI1 max
1500.000
1800.000
13.18
AO1 source max
1500.0
1800.0
22.26
Constant speed 1
300.00 rpm
360.00 rpm
22.27
Constant speed 2
600.00 rpm
720.00 rpm
22.28
Constant speed 3
900 .00 rpm
1080.00 rpm
22.29
Constant speed 4
1200.00 rpm
1440.00 rpm
22.30
Constant speed 5
1500.00 rpm
1800.00 rpm
22.31
Constant speed 6
2400.00 rpm
2880.00 rpm
22.32
Constant speed 7
3000.00 rpm
3600.00 rpm
28.26
Constant frequency 1
5.00 Hz
6.00 Hz
28.27
Constant frequency 2
10.00 Hz
12.00 Hz
28.28
Constant frequency 3
15.00 Hz
18.00 Hz
28.29
Constant frequency 4
20.00 Hz
24.00 Hz
28.30
Constant frequency 5
25.00 Hz
30.00 Hz
28.31
Constant frequency 6
40.00 Hz
48.00 Hz
28.32
Constant frequency 7
50.00 Hz
60.00 Hz
30.11
Minimum speed
-1500.00 rpm
-1800.00 rpm
30.12
Maximum speed
1500.00 rpm
1800.00 rpm
30.13
Minimum frequency
-50.00 Hz
-60.00 Hz
30.14
Maximum frequency
50.00 Hz
60.00 Hz
31.26
Stall speed limit
150.00 rpm
180.00 rpm
31.27
Stall frequency limit
15.00 Hz
18.00 Hz
31.30
Overspeed trip margin
500.00 rpm
500.00 rpm
46.01
Speed scaling
1500.00 rpm
1800.00 rpm
46.02
Frequency scaling
50.00 Hz
60.00 Hz
ACS380 FW.book Page 354 Friday, May 4, 2018 4:18 PM
ghv Vertriebs-GmbH
| Am Schammacher Feld 47 | 85567 Grafing | T 49 80 92 81 89 0 | [email protected] |
www.ghv.de