Parameters 289
46
46 Monitoring/scaling
settings
Speed supervision settings; actual signal filtering; general
scaling settings.
46.01
Speed scaling
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group
23 Speed reference ramp
). The speed acceleration and
deceleration ramp times are therefore related to this value
(
not
to parameter
30.12
Maximum speed
).
Also defines the 16-bit scaling of speed-related
parameters. The value of this parameter corresponds to
20000 in eg. fieldbus communication.
1500.00 rpm
0.10…30000.00 rpm
Acceleration/deceleration terminal/initial speed.
1 = 1 rpm
46.02
Frequency scaling
Defines the maximum frequency value used to define the
acceleration ramp rate and the initial frequency value
used to define deceleration ramp rate (see parameter
group
28 Frequency reference chain
). The frequency
acceleration and deceleration ramp times are therefore
related to this value (
not
to parameter
30.14
Maximum
frequency
.
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds to
20000 in eg. fieldbus communication.
50.00 Hz
0.10…1000.00 Hz
Acceleration/deceleration terminal/initial frequency.
10 = 1 Hz
46.03
Torque scaling
Defines the 16-bit scaling of torque parameters. The value
of this parameter (in percent of nominal motor torque)
corresponds to 10000 in eg. fieldbus communication.
100.0%
0.1…1000.0%
Torque corresponding to 10000 on fieldbus.
10 = 1%
46.04
Power scaling
Defines the output power value that corresponds to 10000
in eg. fieldbus communication. The unit is selected by
parameter
96.16
Unit selection
.
1000.00
0.10…30000.00
Power corresponding to 10000 on fieldbus.
1 = 1 unit
46.05
Current scaling
Defines the 16-bit scaling of current parameters. The
value of this parameter corresponds to 10000 in fieldbus
communication.
10000 A
0…30000 A
46.06
Speed ref zero scaling
Defines a speed corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface FBA A). For example, with a setting
of 500, the fieldbus reference range of 0…20000 would
correspond to a speed of 500…[
46.01
] rpm.
Note:
This parameter is effective only with the ABB Drives
communication profile.
0.00 rpm
0.00 … 30000.00 rpm
Speed corresponding to minimum fieldbus reference.
1 = 1 rpm
46.07
Frequency ref zero
scaling
Defines a frequency corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface FBA A or FBA B). For example, with
a setting of 30, the fieldbus reference range of 0…20000
would correspond to a speed of 30…[
46.02
] Hz.
Note:
This parameter is effective only with the ABB Drives
communication profile.
0.00 Hz
0.00 … 1000.00 Hz
Speed corresponding to minimum fieldbus reference.
10 = 1 Hz
No.
Name/Value
Description
Default
FbEq 16