Fieldbus control through the embedded fieldbus interface (EFB) 465
References for the Transparent 32 profile
The reference values can be written to the objects 2002h and 2003h.
Actual values for the Transparent 32 profile
The actual values can be read from the objects 2005h and 2006h.
Object dictionary
The Object dictionary consists of objects. Each object within the dictionary is
addressed using a 16-bit index (hexadecimal values 0000h-FFFFh). The object
addresses are divided in this manual into three categories:
1.
Communication profile area (1000...1FFF)
Lists the communication related objects.
2.
Manufacturer specific profile area (2000...5FFF)
Lists the manufacturer specific objects.
3.
Standardized profile area (6000...9FFF)
Lists the CiA standard profile objects.
14
EXT2_ACT
1
External control location EXT2 is active.
0
External control location EXT1 is active.
15
FAULT
1
Drive is faulted.
0
Drive is not faulted.
16
ALARM
1
Warning/Alarm is active.
0
No warning/alarm.
17
Reserved
18
Reserved for
DIRECTION_LO
CK
Not yet implemented.
19...21 Reserved
22
USER_0
Status bits that can be combined with drive logic for
application-specific functionality.
23
USER_1
24
USER_2
25
USER_3
26
REQ_CTL
1
Control is requested in this channel.
0
Control is not requested in this channel.
27...31 Reserved
Bit
Name
Value
State/Description
ACS380 FW.book Page 465 Friday, May 4, 2018 4:18 PM
ghv Vertriebs-GmbH
| Am Schammacher Feld 47 | 85567 Grafing | T 49 80 92 81 89 0 | [email protected] |