42 Control macros
Default control connections for the Motor potentiometer macro
This connection diagram is valid for drives with the standard drive variant
ACS380-04xS and the configured drive variant ACS380-04xC +L538 (with the Motor
potentiometer macro selected).
Notes
:
Terminal sizes: 0.14 mm² … 1.5 mm²
Tightening torque: 0.5 N·m (0.4 lbf·ft).
Terminals
Description
Digital I/O connections
Aux. +24 V DC, max 200 mA
Aux. voltage output common
Digital input common
Stop (0) / Start (1)
Forward (0) / Reverse (1)
Frequency / speed up
1)
Frequency / speed down
1)
Constant speed sel 1
2)
Ready run (0) / Not ready run (1)
Digital output auxiliary voltage
Digital input/output common
Analog I/O
Not configured
4)
Analog input circuit common
Not configured
4)
Analog input circuit common
Not configured
Analog output circuit common
Signal cable shield (screen)
Ref. v10 V DC
Safe torque off (STO)
Safe torque off. Connected at factory.
Drive starts only if both circuits are closed.
Relay output
No Fault [Fault (-1)]
3)