Parameters 333
Clear all
All editable parameter values are restored to default
values, except
• end user texts, such as customized warnings and faults
(external faults and changed), and the drive name
• control panel/PC communication settings
• fieldbus adapter settings (clears entire existing
settings)
• control macro selection and the parameter defaults
implemented by it
• parameter
95.20
HW options word 1
and the
differentiated defaults implemented by it.
• user lock configuration parameters
96.100
…
96.102
.
PC tool communication is interrupted during the restoring.
62
Reset all fieldbus
settings
Restores all fieldbus and communication related settings
to default values.
Note
: Fieldbus, control panel and PC tool communication
are interrupted during the restore.
32
Reset home view
Restores the Home view layout to show the values of the
default parameters defined by the control macro use.
512
Reset end user texts
Restores all end user texts to default values, including the
drive name, contact info, customized fault and warning
texts, PID unit and currency unit.
1024
Reset motor data
Restores all motor nominal values and motor ID run
results to default values.
2
All to factory defaults
Restores all drive parameters and settings back to initial
factory values, except
• parameter 95.20 HW options word 1 and the
differentiated defaults implemented by it.
34560
96.07
Parameter save
manually
Saves the valid parameter values to the permanent
memory on the drive control board to ensure that
operation can continue after cycling the power. Save the
parameters with this parameter
• to store values sent from the fieldbus
• when using ex24 V DC power supply to the
control unit: to save parameter changes before you
power down the control unit. The supply has a very
short hold-up time when powered off.
Note:
A new parameter value is saved automatically when
changed from the PC tool or control panel but not when
altered through a fieldbus adapter connection.
Done
Done
Save completed.
0
Save
Save in progress.
1
96.08
Control board boot
Changing the value of this parameter to 1 reboots the
control unit (without requiring a power off/on cycle of the
complete drive module).
The value reverts to 0 automatically.
0
0
No action
1 = 1
1
Reboot the control unit.
96.10
User set status
Shows the status of the user parameter sets.
This parameter is read-only.
See also section
User parameter sets
(page
106
).
-
n/a
No user parameter sets have been saved.
0
No.
Name/Value
Description
Default
FbEq 16