Parameters 157
In1P Start; In2 Stop;
In3 Dir
The sources of the start and stop commands are selected
by parameters
20.03
Ext1 in1 source
and
20.04
Ext1 in2
source
. The source selected by
20.05
Ext1 in3 source
determines the direction. The state transitions of the
source bits are interpreted as follows:
Notes:
• Parameter
20.02
Ext1 start trigger type
has no effect
with this setting.
• When source 2 is 0, the Start and Stop keys on the
control panel are disabled.
5
In1P Start fwd; In2P
Start rev; In3 Stop
The sources of the start and stop commands are selected
by parameters
20.03
Ext1 in1 source
,
20.04
Ext1 in2
source
and
20.05
Ext1 in3 source
. The source selected by
20.05
Ext1 in3 source
determines the direction. The state
transitions of the source bits are interpreted as follows:
Note:
Parameter
20.02
Ext1 start trigger type
has no
effect with this setting.
6
Control panel
Start; stop and direction commands through control panel;
when EXT1 is active. Applies also for PC-Tool when it is
connected via panel port.
11
Fieldbus A
The start and stop commands are taken from fieldbus
adapter A.
Note:
The start signal is always level-triggered with this
setting regardless of parameter
20.02
Ext1 start trigger
type
.
12
Embedded fieldbus
The start and stop commands are taken from the
embedded fieldbus interface.
Note:
The start signal is always level-triggered with this
setting regardless of parameter
20.02
Ext1 start trigger
type
.
14
Integrated Panel
Start; stop and direction commands from Integrated Panel 23
20.02
Ext1 start trigger type
Defines whether the start signal for external control
location EXT1 is edge-triggered or level-triggered.
Note:
This parameter is not effective if a pulse-type start
signal is selected. See the descriptions of the selections of
parameter
20.01
Ext1 commands
.
Level
Edge
The start signal is edge-triggered.
0
Level
The start signal is level-triggered.
1
No.
Name/Value
Description
Default
FbEq 16
State of
source 1
(
20.03
)
State of
source 2
(
20.04
)
State of
source 3
(
20.05
)
Command
0 -> 1
1
0
Start forward
0 -> 1
1
1
Start reverse
Any
0
Any
Stop
State of
source 1
(
20.03
)
State of
source 2
(
20.04
)
State of
source 3
(
20.05
)
Command
0 -> 1
Any
1
Start forward
Any
0 -> 1
1
Start reverse
Any
Any
0
Stop
ACS380 FW.book Page 157 Friday, May 4, 2018 4:18 PM