![ABB ACS380 Series Firmware Manual Download Page 301](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560301.webp)
Parameters 301
Act1 16bit
Actual value ACT1 (16 bits)
5
Act2 16bit
Actual value ACT2 (16 bits)
6
CW 32bit
Control Word (32 bits)
11
Ref1 32bit
Reference REF1 (32 bits)
12
Ref2 32bit
Reference REF2 (32 bits)
13
SW 32bit
Status Word (32 bits)
14
Act1 32bit
Actual value ACT1 (32 bits)
15
Act2 32bit
Actual value ACT2 (32 bits)
16
SW2 16bit
Status Word 2 (16 bits)
24
Other
Source selection (see
Terms and abbreviations
).
-
…
…
…
…
52.12
FBA A data in12
See parameter
52.01
FBA A data in1
.
None
53
53 FBA A data out
Selection of data to be transferred from fieldbus controller
to drive through fieldbus adapter A.
Note:
32-bit values require two consecutive parameters.
Whenever a 32-bit value is selected in a data parameter,
the next parameter is automatically reserved.
53.01
FBA A data out1
Parameters
53.01
…
53.12
select data to be transferred
from the fieldbus controller to the drive through fieldbus
adapter A.
None
None
None.
0
CW 16bit
Control Word (16 bits)
1
Ref1 16bit
Reference REF1 (16 bits)
2
Ref2 16bit
Reference REF2 (16 bits)
3
CW 32bit
Control Word (32 bits)
11
Ref1 32bit
Reference REF1 (32 bits)
12
Ref2 32bit
Reference REF2 (32 bits)
13
CW2 16bit
Control Word 2 (16 bits)
21
Other
Source selection (see
Terms and abbreviations
).
-
…
…
…
…
53.12
FBA A data out12
See parameter
53.01
FBA A data out1
.
None
58
58 Embedded fieldbus
Configuration of the embedded fieldbus (EFB) interface.
See chapter
Fieldbus control through the embedded
fieldbus interface (EFB)
.
NOTE:
Different embedded fieldbus protocols (Modbus or
CANopen) require different hardware options.
58.01
Protocol enable
Enables/disables the embedded fieldbus interface and
selects the protocol to use.
None
None
None (communication disabled).
0
Modbus RTU
Embedded fieldbus interface is enabled and uses the
Modbus RTU protocol.
1
CANopen
Embedded fieldbus interface is enabled and uses the
CANopen protocol.
3
No.
Name/Value
Description
Default
FbEq 16
ACS380 FW.book Page 301 Friday, May 4, 2018 4:18 PM
ghv Vertriebs-GmbH
| Am Schammacher Feld 47 | 85567 Grafing | T 49 80 92 81 89 0 | [email protected] |
www.ghv.de