228 Parameters
31.23
Wiring or earth fault
Selects how the drive reacts to incorrect input power and
motor cable connection (ie. input power cable is
connected to drive motor connection).
Fault
No action
No action taken.
0
Fault
The drive trips on fault
3181
Cross connection
.
1
31.24
Stall function
Selects how the drive reacts to a motor stall condition.
A stall condition is defined as follows:
• The drive exceeds the stall current limit (
31.25
Stall
current limit
)
, and
• the output frequency is below the level set by
parameter
31.27
Stall frequency limit
or the motor
speed is below the level set by parameter
31.26
Stall
speed limit
, and
• the conditions above have been true longer than the
time set by parameter
31.28
Stall time
.
No action
No action
None (stall supervision disabled).
0
Warning
The drive generates an
A780
Motor stall
warning.
1
Fault
The drive trips on fault
7121
Motor stall
.
2
31.25
Stall current limit
Stall current limit in percent of the nominal current of the
motor. See parameter
31.24 Stall function
.
200.0%
0.0…1600.0%
Stall current limit.
-
31.26
Stall speed limit
Stall speed limit in rpm. See parameter
31.24 Stall
function
.
150.00 rpm
0.00…10000.00 rpm
Stall speed limit.
See par.
46.01
31.27
Stall frequency limit
Stall frequency limit. See parameter
31.24 Stall function
.
Note:
Setting the limit below 10 Hz is not recommended.
15.00 Hz
0.00…1000.00 Hz
Stall frequency limit.
See par.
46.02
31.28
Stall time
Stall time. See parameter
31.24 Stall function
.
20 s
0…3600 s
Stall time.
-
No.
Name/Value
Description
Default
FbEq 16