304 Parameters
58.07
Communication
diagnostics
Displays the status of the EFB communication.
This parameter is read-only.
Note that the name is only visible when the error is
present (bit value is 1).
Note
: If parameter
58.01
= [3] CANopen, this parameter is
hidden.
-
0000h…FFFFh
EFB communication status.
1 = 1
58.08
Received packets
Displays a count of valid packets addressed to the drive.
During normal operation, this number increases
constantly.
Can be reset from the control panel by keeping Reset
down for over 3 seconds.
Note
: If parameter
58.01
= [3] CANopen, this parameter is
hidden.
-
0…4294967295
Number of received packets addressed to the drive.
1 = 1
58.09
Transmitted packets
Displays a count of valid packets transmitted by the drive.
During normal operation, this number increases
constantly.
Can be reset from the control panel by keeping Reset
down for over 3 seconds.
Note
: If parameter
58.01
= [3] CANopen, this parameter is
hidden.
-
0…4294967295
Number of transmitted packets.
1 = 1
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Description
0
Init failed
1 = EFB initialization failed
1
Addr config err
1 = Node address not allowed by protocol
2
Silent mode
1 = Drive not allowed to transmit
0 = Drive allowed to transmit
3
Autobauding
4
Wiring error
1 = Errors detected (A/B wires possibly swapped)
5
Parity error
1 = Error detected: check parameters
58.04
and
58.05
6
Baud rate error
1 = Error detected: check parameters
58.05
and
58.04
7
No bus activity
1 = 0 bytes received during last 5 seconds
8
No packets
1 = 0 packets (addressed to any device) detected during last 5
seconds
9
Noise or addressing
error
1 = Errors detected (interference, or another device with the
same address on line)
10
Comm loss
1 = 0 packets addressed to the drive received within timeout
(
58.16
)
11
CW/Ref loss
1 = No control word or references received within timeout (
58.16
)
12
Not active
Reserved
13
Protocol 1
Reserved
14
Protocol 2
Reserved
15
Internal error
1 = Internal errors detected