310 Parameters
58.33
Addressing mode
Defines the mapping between parameters and holding
registers in the 400101…465535 Modbus register range.
Changes to this parameter take effect after the control unit
is rebooted or the new settings validated by parameter
58.06
Communication control
(
Refresh settings
).
Note
: If parameter
58.01
= [3] CANopen, this parameter is
hidden.
Mode 0
Mode 0
16-bit values (groups 1…99, indexes 1…99):
Register address = 100 × parameter group +
parameter index. For example, parameter 22.80 would be
mapped to register 2200 + 80 = 402280.
32-bit values (groups 1…99, indexes 1…99):
Register address = 200 × parameter group +
2 × parameter index. For example, parameter 22.80
would be mapped to register 4400 + 160 =
424560.
0
Mode 1
16-bit values (groups 1…255, indexes 1…255):
Register address = 256 × parameter group +
parameter index. For example, parameter 22.80 would be
mapped to register 5632 + 80 = 405712.
1
Mode 2
32-bit values (groups 1…127, indexes 1…255):
Register address = 512 × parameter group +
2 × parameter index. For example, parameter 22.80
would be mapped to register 11264 + 160 =
411424.
2
58.34
Word order
Selects in which order 16-bit registers of 32-bit
parameters are transferred.
For each register, the first byte contains the high order
byte and the second byte contains the low order byte.
Changes to this parameter take effect after the control unit
is rebooted or the new settings validated by parameter
58.06
Communication control
(
Refresh settings
).
Note
: If parameter
58.01
= [3] CANopen, this parameter is
hidden.
LO-HI
HI-LO
The first register contains the high order word, the second
contains the low order word.
0
LO-HI
The first register contains the low order word, the second
contains the high order word.
1
58.70
EFB debug mode
This parameter enables debug mode. RAW-data is
echoed to drive parameters
58.18
EFB control word
,
58.71
EFB reference 1
,
58.72
EFB reference 2
,
58.19
EFB status word
,
58.73
EFB actual value 1
and
58.74
EFB actual value 2
Changes to this parameter take effect after the control unit
is rebooted or the new settings validated by parameter
58.06
Communication control
(
Refresh settings
).
Note
: If parameter
58.01
= [1] Modbus RTU, this
parameter is hidden.
1
Disable
Debug mode disabled.
58.18
EFB control word
,
58.71
EFB reference 1
,
58.72
EFB reference 2
,
58.19
EFB
status word
,
58.73
EFB actual value 1
and
58.74
EFB
actual value 2
are not updated.
0
No.
Name/Value
Description
Default
FbEq 16