40.55
Set 1 trim adjust
Defines a multiplier for the trimming factor. This value is
multiplied by the result of parameter
40.51
Set 1 trim
mode
. Consequently, the result of the multiplication is
used to multiply the result of parameter
40.56
Set 1 trim
source
.
1.000
-100.000...100.000
Multiplier for trimming factor.
1 = 1
40.56
Set 1 trim source
Selects the reference to be trimmed.
PID ref
PID ref
PID setpoint.
1
PID output
PID controller output.
2
40.57
PID set1/set2
selection
Selects the source that determines whether process PID
parameter set 1 (parameters
40.07
…
40.50
) or set 2
(group
41 Process PID set 2
) is used.
0 = PID set 1 in use
1 = PID set 2 in use
PID set 1
PID set 1
PID set 1.
0
PID set 2
PID set 2.
1
DI1
Digital input DI1 (
10.02
DI delayed status
, bit 0).
2
DI2
Digital input DI2 (
10.02
DI delayed status
, bit 1).
3
DI3
Digital input DI3 (
10.02
DI delayed status
, bit 2).
4
DI4
Digital input DI4 (
10.02
DI delayed status
, bit 3).
5
DIO1
Digital input/output DIO1 (
11.02
DIO delayed status
, bit 0). 10
DIO2
Digital input/output DIO2 (
11.02
DIO delayed status
, bit 1) 11
Timed function 1
Bit 0 of
34.01 Timed functions status
.
18
Timed function 2
Bit 1 of
34.01 Timed functions status
.
19
Timed function 3
Bit 2 of
34.01 Timed functions status
.
20
Supervision 1
Bit 0 of
32.01 Supervision status
21
Supervision 2
Bit 1 of
32.01 Supervision status
22
Supervision 3
Bit 2 of
32.01 Supervision status
.
23
Other [bit]
Source selection (see
Terms and abbreviations
).
-
40.58
Set 1 increase
prevention
Prevention of PID integration term increase for PID set 1.
No
No
Increase prevention not in use.
0
Limiting
The PID integration term is not increased if the maximum
value for the PID output is reached. This parameter is
valid for the PID set 1.
1
Ext PID min lim
The process PID integration term is not increased when
the output of the external PID has reached it's minimum
limit. In this setup, the external PID is used as a source for
the process PID. This parameter is valid for the PID set 1.
2
Ext PID max lim
The process PID integration term is not increased when
the output of the external PID has reached it's maximum
limit. In this setup, the external PID is used as a source for
the process PID. This parameter is valid for the PID set 1.
3
40.59
Set 1 decrease
prevention
Prevention of PID integration term decrease for PID set 1.
No
No
Decrease prevention not in use.