200 Parameters
26.11
Torque ref1 source
Selects torque reference source 1.
Two signal sources can be defined by this parameter and
26.12
Torque ref2 source
. A digital source selected by
26.14
Torque ref1/2 selection
can be used to switch
between the two sources, or a mathematical function
(
26.13
Torque ref1 function
) applied to the two signals to
create the reference.
Zero
Zero
None.
0
AI1 scaled
12.12
AI1 scaled value
(see page
142
).
1
AI2 scaled
12.22
AI2 scaled value
(see page
144
).
2
FB A ref1
03.05
FB A reference 1
(see page
119
).
4
FB A ref2
03.06
FB A reference 2
(see page
119
).
5
EFB ref1
03.09
EFB reference 1
(see page
119
).
8
EFB ref2
03.10
EFB reference 2
(see page
119
).
9
Motor potentiometer
22.80 Motor potentiometer ref act
(output of the motor
potentiometer).
15
PID
40.01
Process PID output actual
(output of the process
PID controller).
16
Frequency input
11.38
Freq in 1 actual value
(when DI3 or DI4 is used as a
frequency input).
17
Control panel (ref
saved)
Panel reference (
03.01
Panel reference
, see page
118
)
saved by the control system for the location where the
control returns is used as the reference.
18
No.
Name/Value
Description
Default
FbEq 16
26.14
1
0
26.11
0
AI
FB
26.12
26.72
26.71
…
Other
…
0
AI
FB
…
Other
…
26.13
MUL
SUB
ADD
MIN
MAX
Ref1
26.70
Ext1 -> Ext2
t
Reference
Ext1 reference
Ext2 reference
Active reference
Inactive reference
ACS380 FW.book Page 200 Friday, May 4, 2018 4:18 PM