![ABB ACS380 Series Firmware Manual Download Page 455](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560455.webp)
Fieldbus control through the embedded fieldbus interface (EFB) 455
Status Word for the ABB Drives profile
Status word of the ABB Drives profile can be read from the object 2104h, or
alternatively from the object 6041h.
The table below shows the fieldbus Status Word for the ABB Drives control profile.
The embedded fieldbus interface converts the drive Status Word into this form for the
fieldbus. The upper case boldface text refers to the states shown in
State transition
diagram for the ABB Drives profile
on page
431
.
7
RESET
0=>1
Fault reset if an active fault exists. Proceed to
SWITCH-ON INHIBITED.
Note
: This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0
No warning/alarm.
8
JOGGING 1
1
Request running at Jogging 1 speed.
Note
: This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0
Continue normal operation.
9
JOGGING 2
1
Request running at Jogging 2 speed.
Note: This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0
Continue normal operation.
10
REMOTE CMD
1
Fieldbus control enabled.
0
Control Word <> 0 or Reference <> 0: Retain last
Control Word and Reference. Control Word = 0 and
Reference = 0: Fieldbus control enabled. Reference
and deceleration/acceleration ramp are locked.
11
EXT CTRL LOC
1
Select External Control Location EXT2. Effective if the
control location is parameterized to be selected from
the fieldbus.
0
Select External Control Location EXT1. Effective if the
control location is parameterized to be selected from
the fieldbus.
12
USER_0
Writable control bits that can be combined with drive
logic for application-specific functionality.
13
USER_1
14
USER_2
15
USER_3
Bit
Name
Value
State/Description
0
RDY_ON
1
READY TO SWITCH ON
.
0
NOT READY TO SWITCH ON
.
1
RDY_RUN
1
READY TO OPERATE
.
0
OFF1 ACTIVE
.
Bit
Name
Value
State/Description
ACS380 FW.book Page 455 Friday, May 4, 2018 4:18 PM
ghv Vertriebs-GmbH
| Am Schammacher Feld 47 | 85567 Grafing | T 49 80 92 81 89 0 | [email protected] |
www.ghv.de