132 Parameters
10.03
DI force selection
Selects the digital inputs, states of which will be controlled
by parameter
10.04
DI forced data
. A bit in parameter
10.04
DI forced data
is provided for each digital input, and
its value is applied whenever the corresponding bit in this
parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
10.03
and
10.04
).
0000h
0000h…FFFFh
Override selection for digital inputs.
1 = 1
10.04
DI forced data
Defines the forced values for the digital inputs selected by
parameter
10.03 DI force selection
. It is only possible to
force an input that has been selected in parameter
10.03
DI force selection
.
Bit 0 is the forced value for DI1.
0000h
0000h…FFFFh
Forced values of digital inputs.
1 = 1
10.21
RO status
Status of relay outputs R01...RO3.
-
0000h…FFFFh
Status of relay outputs.
1 = 1
No.
Name/Value
Description
Default
FbEq 16
Bit
Value
0
1 = Force DI1 to value of bit 0 of parameter
10.04
DI forced data
.
1
1 = Force DI2 to value of bit 1 of parameter
10.04
DI forced data
.
2
1 = Force DI3 to value of bit 2 of parameter
10.04
DI forced data
.
3
1 = Force DI4 to value of bit 3 of parameter
10.04
DI forced data
.
4
1 = Force DI5 to value of bit 4 of parameter
10.04
DI forced data
.
5
1 = Force DI6 to value of bit 5 of parameter
10.04
DI forced data
.
6...15
Reserved.
Bit
Value
0
Force the value of this bit to D1, if so defined in parameter
10.03
DI force selection
.
1
Force the value of this bit to D2, if so defined in parameter
10.03
DI force selection
.
2
Force the value of this bit to D3, if so defined in parameter
10.03
DI force selection
.
3
Force the value of this bit to D4, if so defined in parameter
10.03
DI force selection
.
4
Force the value of this bit to D5, if so defined in parameter
10.03
DI force selection
.
5
Force the value of this bit to D6, if so defined in parameter
10.03
DI force selection
.
6...15 Reserved.
Bit
Value
0
1 = RO1 is energized.
1
1 = RO2 is energized.
2
1 = RO3 is energized.
3...15 Reserved.
ACS380 FW.book Page 132 Friday, May 4, 2018 4:18 PM