![ABB ACS380 Series Firmware Manual Download Page 290](http://html.mh-extra.com/html/abb/acs380-series/acs380-series_firmware-manual_2560290.webp)
290 Parameters
46.11
Filter time motor
speed
Defines a filter time for signals
01.01
Motor speed used
and
01.02
Motor speed estimated
.
500 ms
2…20000 ms
Motor speed signal filter time.
1 = 1 ms
46.12
Filter time output
frequency
Defines a filter time for signal
01.06
Output frequency
.
500 ms
2…20000 ms
Output frequency signal filter time.
1 = 1 ms
46.13
Filter time motor
torque
Defines a filter time for signal
01.10 Motor torque
.
100 ms
2…20000 ms
Motor torque signal filter time.
1 = 1 ms
46.14
Filter time power
Defines a filter time for signal
01.14 Output power
.
100 ms
2…20000 ms
Output power signal filter time.
1 = 1 ms
46.21
At speed hysteresis
Defines the “at setpoint” limits for speed control of the
drive.
When the difference between reference (
22.87
Speed
reference act 7
) and the speed (
24.02
Used speed
feedback
) is smaller than
46.21
At speed hysteresis
, the
drive is considered to be “at setpoint”. This is indicated by
bit 8 of
06.11
Main status word
.
50.00 rpm
0.00…30000.00 rpm
Limit for “at setpoint” indication in speed control.
See par.
46.01
No.
Name/Value
Description
Default
FbEq 16
24.02
(rpm)
0 rpm
22.87
+
46.21
(rpm)
22.87
(rpm)
22.87
-
46.21
(rpm)
Drive at setpoint
(
06.11
bit 8 = 1)
ACS380 FW.book Page 290 Friday, May 4, 2018 4:18 PM