Table 62: Programmable
Button
Access level
Description
Manual pump
(enable/disable) Operator
This key allows the user to enable and disable the variable speed oil pump. The
pump will be allowed to run for a maximum of 10 minutes. If a longer running time
is desired, it must be enabled again. Manual oil pump control is prevented (and
the button is not displayed) during system pre-lube, system run, proximity probe
calibration, seal lubrication and system coastdown.
Standby lube
(enabled/
disabled)
Service
Allows the user to Enable or Disable the Standby Lube operation. When Enabled,
this feature causes the Variable speed Oil Pump to operate for 2 minutes at 24 hour
intervals while the chiller is shutdown.
Pressure setpoint Service
This key allows the user to define the oil pressure setpoint that compressor #1
Variable Speed Oil Pump will control to during automatic speed control operation.
Range is 20.0 to 45.0 psid, Default 35.0 psid.
Control period
Service
Allows the user to define the output interval of the increment or decrement speed
commands to the compressor Variable Speed Oil Pump. Presently, it is set to 0.9
seconds and cannot be changed.
Variable speed
oil pump speed
control: Raise
Service
With the Oil Pump running, this key puts compressor #1 Variable Speed Oil Pump into
manual speed control mode and increments the speed command by 0.5 Hz each time
it is pressed.
Variable speed
oil pump speed
control: Lower
Service
With the Oil Pump running, this key puts compressor #1 Variable Speed Oil Pump into
manual speed control mode and decrements the speed command by 0.5 Hz each time
it is pressed.
Variable speed
oil pump speed
control: Set
Service
This key allows the user to specify a fixed speed at which compressor #1 Variable
Speed Oil Pump will run when in manual speed control mode. The range is 25 Hz to 60
Hz.
Variable speed
oil pump speed
control: Auto
Service
This key returns compressor #1 Variable Speed Oil Pump control to automatic speed
control mode, where the speed command is based on the Oil Pressure Setpoint.
Table 63: Navigation
Button
Access level
Description
Home
View
Returns to the Home screen.
Oil sump
View
Returns to the Oil sump screen.
75
Model YD Mod D with OptiView Control Center
Содержание YD Mod D
Страница 2: ...2 Model YD Mod D with OptiView Control Center...
Страница 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Страница 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Страница 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Страница 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Страница 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Страница 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Страница 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Страница 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Страница 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Страница 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Страница 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Страница 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Страница 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Страница 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Страница 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Страница 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...