Table 40: Display only fields for dual compressor operation
Field/LED name
Description
Surge window time
When the lag compressor is started, this value counts up from 1 minute to the time
programmed as the COUNT WINDOW Setpoint. When it reaches a count equal to
the COUNT WINDOW setpoint, it doesn’t increment anymore and the number of
dual compressor surge events in the oldest minute is discarded and the number of
dual–compressor surge events in the most recent minute are added, thus providing
a rolling count of the total dual-compressor surge events that have occurred within
the last number of minutes displayed as the SURGE WINDOW TIME. This value is reset
when one or both compressors have shutdown.
Surge window count
Displays the number of dual-compressor surge events that have occurred in the last
15 to 120 minutes (as programmed with the COUNT WINDOW setpoint). If the lag
compressor has been running for less than the COUNT WINDOW setpoint minutes,
it is the number of dual-compressor surge events that have occurred within the last
number of minutes displayed as the SURGE WINDOW TIME. The count is cleared when
the one or both compressors have shutdown.
Total surge count
Displays the total number of dual-compressor surge events detected over the lifetime
of the chiller.
Surge detected (LED)
Lights for 5 seconds each time a dual-compressor surge is detected.
Lead compressor
Identifies the compressor that has been assigned as the lead compressor.
Lead % Full Load Amps
Displays the motor current of the lead compressor as a percentage of the Full Load
Amps of that compressor motor.
Lead PRV position
Displays the position of the lead compressor pre-rotation vanes.
Lead variable geometry diffuser
position
Displays the position of the lead compressor VGD.
Lag % Full Load Amps
Displays the motor current of the lag compressor as a percentage of the Full Load
Amps of that compressor motor.
Lag PRV position
Displays the position of the lag compressor pre-rotation vanes.
Lag variable geometry diffuser
position
Displays the position of the lag compressor VGD.
Programmable
None
Table 41: Navigation
Button
Access level
Description
Home
View
Returns to the Home screen.
Compressor
View
Returns to the Compressor screen.
Single
compressor setup
View
Displays a subscreen that allows viewing and programming of the surge protection
applied when only one compressor is running.
Dual compressor
setup
View
Displays a subscreen that allows viewing and programming of the surge protection
applied when both compressors are running.
Model YD Mod D with OptiView Control Center
56
Содержание YD Mod D
Страница 2: ...2 Model YD Mod D with OptiView Control Center...
Страница 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Страница 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Страница 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Страница 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Страница 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Страница 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Страница 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Страница 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Страница 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Страница 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Страница 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Страница 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Страница 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Страница 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Страница 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Страница 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...