Table 143: Safety shutdown messages
Message
Description
OIL PUMP #1 – LOW
DIFFERENTIAL PRESSURE
The chiller (both compressors) has been shutdown because the differential oil pressure,
as sensed by compressor #1 Pump transducer and the Sump transducer, decreased to
<15.0 PSID while compressor #1 was running or went below 25.0 PSID during the last 5
seconds of compressor #1 Prelube. This fault is only checked if both the compressor #1
Pump transducer and the Sump transducer are in range. The chiller can be started after the
Clear Faults button is pressed.
OIL PUMP #2 – LOW
DIFFERENTIAL PRESSURE
The chiller (both compressors) has been shutdown because the differential oil pressure,
as sensed by compressor #2 Pump transducer and the Sump transducer, decreased to
<15.0 PSID while compressor #1 was running or went below 25.0 PSID during the last 5
seconds of compressor #1 Prelube. This fault is only checked if both the compressor #2
Pump transducer and the Sump transducer are in range. The chiller can be started after the
Clear Faults button is pressed.
OIL PUMP #1 – PRESSURE
TRANSDUCER OUT OF RANGE
The Chiller (both compressors) has shutdown because compressor #1 Pump oil pressure
transducer is out of range (< 0.0 psig or >300.0 psig). The chiller can be started after the
pressure is within range and the Operator presses the Clear Faults button.
If compressor #1 is locked-out using the Lockout key on the Capacity Compressor Cycling
Screen, this fault does not cause compressor #2 to shutdown or prevent it from starting.
When this fault occurs on a locked-out compressor, it is displayed as a warning. This allows
the user to know that a fault exists on the locked-out compressor. The condition must be
corrected prior to the lockout being removed from the compressor. If it is not, the warning
condition will revert back to a shutdown as soon as the lockout is removed and will cause the
chiller to trip.
OIL PUMP #2 – PRESSURE
TRANSDUCER OUT OF RANGE
The Chiller (both compressors) has shutdown because compressor #2 Pump oil pressure
transducer is out of range (< 0.0 psig or >300.0 psig). The chiller can be started after the
pressure is within range and the Operator presses the Clear Faults button.
If compressor #2 is locked out using the Lockout key on the Capacity Compressor Cycling
Screen, this fault does not cause compressor #1 to shutdown or prevent it from starting.
When this fault occurs on a locked-out compressor, it is displayed as a warning. This allows
the user to know that a fault exists on the locked-out compressor. The condition must be
corrected prior to the lockout being removed from the compressor. If it is not, the warning
condition will revert back to a shutdown as soon as the lockout is removed and will cause the
chiller to trip.
OIL SUMP – PRESSURE
TRANSDUCER OUT OF RANGE
The chiller (both compressors) has shut down because the Sump oil pressure transducer is
out of range (< 0.0 psig or >300.0 psig). The chiller can be started after the pressure is within
range and the Operator presses the Clear Faults button.
OIL PUMP #1 – SETPOINT
NOT ACHIEVED
The chiller (both compressors) has shutdown because compressor #1 differential oil
pressure, as sensed by compressor #1 Pump transducer and the Sump transducer, failed to
meet the following requirements:
•
The differential oil pressure was <35.0 psid for 5 continuous seconds during the last
10 seconds of compressor #1 prelube or during the first 15 seconds of compressor #1
run.
-OR-
•
After the first 30 seconds of compressor #1 run, the differential oil pressure was < the
Setpoint/Target oil pressure with the oil pump drive speed command at 60 Hz for 5
continuous seconds.
The chiller can be started after the Operator presses the Clear Faults button.
143
Model YD Mod D with OptiView Control Center
Содержание YD Mod D
Страница 2: ...2 Model YD Mod D with OptiView Control Center...
Страница 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Страница 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Страница 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Страница 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Страница 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Страница 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Страница 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Страница 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Страница 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Страница 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Страница 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Страница 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Страница 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Страница 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Страница 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Страница 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...