
Table 137: Status messages
Message
Description
System Run
The chiller is running under the condition described in the Details Line of the Status Bar.
System Coastdown
The chiller has shut down and the Post-run lubrication is being performed.
System Start Inhibit
The chiller is prevented from being started due to the reason displayed on the Details Line of
the Status bar.
Run messages
Table 138: Run messages
Message
Description
Leaving Chilled Liquid
Control
The chiller is running, controlling the
Leaving Chilled Liquid to the Leaving
Chilled Liquid Temperature Setpoint
. There are no system conditions inhibiting this
operation.
System In Lead
Compressor Pulldown
Displayed while a
Lead Compressor Pulldown Time Setpoint
(0-255 minutes) is in
effect. The time remaining in the period is also displayed. For the duration of this period,
only the lead compressor will be permitted to run. The lag compressor will not be brought
on line during this period. A current limit may be applied to the lead motor during this
period using the
Lead Compressor Pulldown Demand Limit Setpoint
(30-100%). See
the complete explanation in
Description of system and fundamentals of operation
Lead Motor-high Current
Limit
Either the
Lead Compressor Pulldown Demand Time Setpoint
is in effect and the lead
compressor motor current is being limited by the
Lead Compressor Pulldown Demand
Limit Setpoint
, or the
Lead Compressor Pulldown Demand Time Setpoint
has
elapsed and the lead compressor motor current is being limited by the
Chiller Current
Limit Setpoint
.
Refer to the
for details of the conditions above.
When the motor current increases to the
inhibit open
threshold, the pre-rotation vanes are
inhibited from further opening. This prevents a further current rise. If the current continues
to rise to the
start close
threshold, the Vanes begin closing until the current falls to the
stop
close
threshold. Automatic vane operation is resumed and this message automatically clears
when the motor current decreases to the
allow open
threshold.
Lag Compressor Prelube
A start has been initiated on the lag compressor and the 50 second pre-start lubrication is
being performed.
Lag Compressor
Coastdown
The lag compressor has shutdown and the 150 second post-run lubrication is being
performed on the lag compressor.
Lag Compressor
Unloading Before
Shutdown
Displayed while the pre-rotation vanes and discharge valves are closing during a soft
shutdown of the lag compressor.
Vanes #1 Start Inhibit-
motor Switch Open
Compressor #1 is inhibited from starting because its pre-rotation vanes are not fully closed
(Vane motor switch open), but compressor #2 is able to run and thus the chiller is not
prevented from operating. This message clears when the vanes have fully closed.
Vanes #2 Start Inhibit-
motor Switch Open
Compressor #2 is inhibited from starting because its pre-rotation vanes are not fully closed
(Vane motor switch open), but compressor #1 is able to run and thus the chiller is not
prevented from operating. This message clears when the vanes have fully closed.
Motor #1 Start Inhibit
– Anti-recycle
Compressor #1 is inhibited from starting because its 30 minute anti-recycle period is in
effect, but compressor #2 is able to run. This message clears when the 30 minute timer
expires.
Motor #2 Start Inhibit
– Anti-recycle
Compressor #2 is inhibited from starting because its 30 minute anti-recycle period is in
effect, but compressor #1 is able to run. This message clears when the 30 minute timer
expires.
Model YD Mod D with OptiView Control Center
130
Содержание YD Mod D
Страница 2: ...2 Model YD Mod D with OptiView Control Center...
Страница 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Страница 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Страница 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Страница 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Страница 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Страница 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Страница 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Страница 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Страница 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Страница 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Страница 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Страница 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Страница 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Страница 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Страница 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Страница 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...