Capacity compressor cycling screen
Figure 24: Capacity compressor cycling screen
This screen allows the user to specify the chiller load conditions under which the lag compressor
is cycled on and off. Both compressors are not started at the same time. The lead compressor is
started first. If it does not meet the load requirements as established with the following setpoints,
the lag compressor is started. After the lag compressor is running, it will be shutdown if the load
decreases to the point established by the following setpoints. Parameters pertinent to chiller
loading are displayed. Also, compressor #1 or #2 can be selected for lockout.
Table 54: Display only fields
Field/LED name
Description
Temperature differential (leaving
chilled liquid temperature - setpoint)
Displays the difference between the Leaving Chilled Liquid Temperature and the
Leaving Chilled Liquid Temperature Setpoint.
Delta T rate
Displays the rate of change of the Leaving Chilled Liquid Temperature as “X.X ºF/
Minute”. Value displayed represents a five-point rolling average obtained as follows:
After the first 3 minutes of chiller run time, the Leaving Chilled Liquid Temperature
is sampled once every minute. The previous reading is subtracted from the present
reading and the last 5 results are averaged to obtain a five-point rolling average.
Displayed as zero when chiller is not running.
Lead % Full Load Amps
Displays the motor current of the lead compressor as a percentage of the Full Load
Amps of that compressor motor.
Lead PRV position
Displays the position of the lead compressor pre-rotation vanes position.
Lead VGD position
Displays the position of the lead compressor Variable Geometry Diffuser.
Lead VSD output frequency
Displays the value of the lead compressor VSD output frequency if a VSD is installed.
Lag % Full Load Amps
Displays the motor current of the lag compressor as a percentage of the Full Load
Amps of that compressor motor.
Lag PRV position
Displays the position of the lag compressor pre-rotation vanes position.
Lag VGD position
Displays the position of the lag compressor Variable Geometry Diffuser.
Lag VSD output frequency
Displays the value of the lag compressor VSD output frequency if a VSD is installed.
Lead compressor
Identifies the compressor that has been assigned as the lead compressor.
High head lag start (LED)
Illuminates when a High Head Lag Start condition exists.
Reduced speed lag start (LED)
Illuminates when the lag compressor is to start if the lead compressor VSD is running
at less than maximum speed.
Model YD Mod D with OptiView Control Center
68
Содержание YD Mod D
Страница 2: ...2 Model YD Mod D with OptiView Control Center...
Страница 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Страница 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Страница 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Страница 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Страница 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Страница 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Страница 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Страница 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Страница 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Страница 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Страница 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Страница 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Страница 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Страница 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Страница 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Страница 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...