Condenser screen
Figure 8: Condenser screen
This screen displays a cutaway view of the chiller condenser. Animation indicates condenser liquid
flow. This screen also serves as a gateway to controlling the Refrigerant Level.
Table 10: Display only fields
Field/LED name
Description
Entering condenser liquid
temperature
Displays the water temperature as it enters the condenser.
Leaving condenser liquid
temperature
Displays the water temperature as it leaves the condenser.
Condenser saturation temperature Displays the saturation temperature in the condenser.
Condenser small temperature
difference
Displays the difference between the Condenser Refrigerant temperature and the
Leaving Condenser Liquid temperature. The Condenser Refrigerant temperature will
be represented by the Condenser Saturation temperature.
Condenser pressure
Displays the refrigerant pressure in the condenser.
Drop leg refrigerant temperature
Displays the temperature of the refrigerant in the drop leg between the condenser
and evaporator shells, if the sensor is present and "Enabled".
Sub-cooling temperature
Displays the difference between the Condenser Refrigerant temperature and the
Drop Leg Refrigerant temperature. The Condenser Refrigerant temperature will be
represented by the Condenser Saturation temperature. If the Drop Leg sensor is not
present, this temperature is not displayed.
Condenser liquid flow switch (open/
closed)
Indicates whether flow is present in the condenser.
Condenser liquid pump (run/stop) Indicates whether Condenser liquid pump is operating.
Condenser refrigerant level
Displays the present position of the refrigerant level.
Active level setpoint
Displays the setpoint to which the refrigerant level is being controlled.
Level control valve command
Displays the current Refrigerant Valve command.
Model YD Mod D with OptiView Control Center
36
Содержание YD Mod D
Страница 2: ...2 Model YD Mod D with OptiView Control Center...
Страница 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Страница 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Страница 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Страница 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Страница 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Страница 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Страница 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Страница 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Страница 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Страница 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Страница 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Страница 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Страница 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Страница 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Страница 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Страница 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...