
Table 45: Display only fields
Field/LED name
Description
Lead VGD position
Displays the position of the lead compressor Variable Geometry Diffuser.
Lag % Full Load Amps
Displays the motor current of the lag compressor as a percentage of the Full Load
Amps of that compressor motor.
Lag PRV position
Displays the position of the lag compressor pre-rotation vanes position.
Lag VGD position
Displays the position of the lag compressor Variable Geometry Diffuser.
Table 46: Programmable
Button
Access level
Description
Count window
Operator
Allows the user to define the period of time (15 to 120 minutes; default 60) in which
the number of surge events are compared to the Count Limit threshold. Each time
a surge occurs, the Surge Window Count increments. If the Surge Window count is
less than or equal to the Count Limit, a close signal is applied to both compressor
#1 and #2 Pre-Rotation Vanes until compressor #1 motor current is within 20% of
compressor #2. While the vanes are closing, “Warning – Anti Surge- Excess Surge
Limit” is displayed until the motor currents are balanced with 20%, whereupon it
automatically clears. If the Surge Window Count exceeds the Count Limit, the lag
compressor is taken off line and “Warning – Anti Surge –Surge Limit Exceeded” is
displayed. This is displayed until manually reset with the Warning Reset Key.
Count limit
Operator
Allows the user to define the maximum number of surge events (2 to 8; default 3)
that can occur within the programmed Count Window period of time before the lag
compressor is taken offline. Each time a surge occurs, the Surge Window Count is
incremented. If the Surge Window Count. If the number of surge events within the
Count window exceeds the Count Limit, the lag compressor is taken off line and
“Warning – Anti Surge – Surge Limit Exceeded” is displayed. This will be displayed until
manually cleared with the Warning Reset key.
Clear surge count Admin
Allows user to reset dual compressor Total Surge Count to zero.
High head DP/P
limit
Service
Specifies the Delta P/P head condition [(Condenser pressure - Evaporator pressure) /
Evaporator pressure], above which the Lead compressor’s Pre-rotation Vanes will be
driven closed while the Lag compressor is starting. This avoids surging during high
head conditions.
Table 47: Navigation
Button
Access level
Description
Home
View
Returns to the Home screen.
Surge
View
Returns to the Main Surge screen.
61
Model YD Mod D with OptiView Control Center
Содержание YD Mod D
Страница 2: ...2 Model YD Mod D with OptiView Control Center...
Страница 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Страница 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Страница 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Страница 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Страница 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Страница 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Страница 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Страница 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Страница 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Страница 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Страница 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Страница 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Страница 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Страница 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Страница 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Страница 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...