Hot gas bypass screen
Figure 17: Hot gas bypass screen
This screen displays a cutaway view of the Hot Gas Bypass Valve. All setpoints relating to Hot Gas
Bypass control are maintained on this screen. Also, related Hot Gas Bypass control parameters are
displayed for reference. Through animation, the relative valve position is displayed. In addition, the
valve can be manually operated.
Note:
Requires access level of SERVICE.
Table 36: Display only fields
Field/LED name
Description
HGBP command
Displays the position of the Hot Gas valve over the range of 0% (closed) to 100% (fully
open). The valve position is animated. When the actual position is 0% to 19%, the
valve is shown fully closed. When actual position is 20% to 39% the valve is shown 25%
open. When actual position is 40% to 59%, the valve is shown 50% open. When actual
position is 60% to 79%, the valve is shown as 75% open. Positions greater than 79%
shown as full open.
Lead PRV position
Displays the position of the Lead Compressor Pre-Rotation Vanes over the range of 0%
(closed) to 100% (fully open). Displayed at XXX until calibration procedure is performed
by service technician.
Delta P/P
Displays the parameter that represents system differential or “Head”. It is calculated
as [(condenser pressure – evaporator pressure) / evaporator pressure].
Temperature differential
Displays the difference between the Leaving Chilled Liquid Temperature and the
Leaving Chilled Liquid Temperature Setpoint. It is calculated by subtracting the
Leaving Chilled Liquid temperature from the Leaving Chilled Liquid Temperature
Setpoint.
Total surge count
Displays the total number of surge events that have been detected over the lifetime of
the chiller.
Lead VGD position
Displays the position of the Lead Compressor VGD over the range of 0% (closed) to
100% (fully open). Displayed at XXX until calibration procedure is performed by service
technician.
Surge detected (LED)
Lights for 5 seconds each time a surge is detected.
53
Model YD Mod D with OptiView Control Center
Содержание YD Mod D
Страница 2: ...2 Model YD Mod D with OptiView Control Center...
Страница 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Страница 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Страница 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Страница 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Страница 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Страница 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Страница 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Страница 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Страница 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Страница 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Страница 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Страница 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Страница 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Страница 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Страница 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Страница 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...