the default language. If a language other than English is being displayed, an English-only speaking
person should navigate to the USER Screen using the preceding Navigation chart and select English
per the USER Screen instructions in this book.
Analog input ranges
The following table indicates the valid display range for each of the analog input values. In the
event that the input sensor is reading a value outside of these ranges, the < or > symbols will be
displayed beside the minimum or maximum value, respectively.
Table 1: Analog input display ranges
English range
Metric range
Analog input
Low
High
Units
Low
High
High
Leaving chilled liquid temperature
0.0
82.0
°F
-17.7
27.7
°C
Return chilled liquid temperature
0.0
94.1
°F
-17.7
34.5
°C
Leaving condenser liquid temperature
8.0
133.5
°F
-13.3
56.3
°C
Return condenser liquid temperature
8.0
133.5
°F
-13.3
56.3
°C
Evaporator refrigerant temperature
(optional)
0.0
126.1
°F
-17.7
52.3
°C
Discharge temperature
31.8
226.3
°F
-0.1
107.9
°C
Oil temperature
31.8
226.3
°F
-0.1
107.9
°C
Condenser pressure
0.0
315.0
psig
0.0
2172.4
kPag
Condenser temperature*
-98.7
160.1
°F
-72.6
71.7
°C
Evaporator pressure
5.5
77.4
psig
37.9
533.7
kPag
Evaporator temperature*
-44.9
64.7
°F
-42.7
18.1
°C
Oil sump pressure
0.0
315.0
psig
0.0
2172.4
kPag
High speed thrust bearing proximity
position
8.0
99.0
mil
8.0
99.0
mil
Refrigerant level
0.0
100.0
%
0.0
100.0
%
Drop leg refrigerant
0.0
121.7
°F
-17.7
49.8
°C
Note:
* Saturation temperatures are calculated values. They will display XXX if the pressure
used for the calculation is out of range.
Model YD Mod D with OptiView Control Center
28
Содержание YD Mod D
Страница 2: ...2 Model YD Mod D with OptiView Control Center...
Страница 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Страница 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Страница 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Страница 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Страница 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Страница 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Страница 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Страница 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Страница 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Страница 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Страница 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Страница 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Страница 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Страница 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Страница 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Страница 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...