Table 14: Programmable
Button
Access level
Description
Level setpoint
Service
Displays the setpoint to which the refrigerant level is being controlled. Adjustable 20 to
80%; default 50%.
Startup position Service
Sets the starting position of the refrigerant valve to allow the system to match the load
quicker. Adjustable 0 to 100%; default 50%.
Startup delay
Admin
The amount of time the refrigerant level valve PID waits after start before it starts
controlling the valve position. This allows the system to stabilize before making valve
position changes. Set at 15 seconds but is adjustable with an Admin password.
Ramp time
Admin
After the chiller has been running for the level control startup delay time, if the
refrigerant level is less than the Level Setpoint, a linearly increasing ramp is applied
to the Level Setpoint. This ramp allows the level to go from the present level to the
programmed Level Setpoint over a period of time programmed as the Ramp Up Time.
This setpoint can only be changed with ADMIN level access. Adjustable 1 to 5 minutes;
default 1.
Lag start setpoint Service
Sets the refrigerant level setpoint for starting the Lag Compressor to help prevent
starving the evaporator and tripping on low evaporator pressure. Adjustable 10 to
90%; default 20%.
Manual
increment
Service
This sets the percentage the refrigerant valve will manually be driven with each press
of the Open or Close buttons. Adjustable 0.1 to 10%; default 1.0%.
Open
Pressing this button will set the Condenser Level Control Valve Mode to Manual
if it had been in Auto and will increase the current Condenser Level Control Valve
Command by an amount equal to the Manual Increment, with a maximum of 100.0%.
Close
Pressing this button will set the Condenser Level Control Valve Mode to Manual if
it had been in Auto and will decrease the current Condenser Level Control Valve
Command by an amount equal to the Manual Increment, with a minimum of 0.0%.
Set
Service
Pressing this button will open a dialog box where the user can manually enter a valve
command. Once a legitimate value has been entered and the Enter key pressed, the
Condenser Level Control Valve Mode shall be set to Manual if it had been in Auto and
the Condenser Level Control Valve Command shall be set to the entered value.
High threshold
Service
Sets the high limit for the Subcooler Effectiveness Warning. Adjustable 0 to 100%;
default 50%.
Low threshold
Service
Sets the low limit for the Subcooler Effectiveness Warning. Adjustable 0 to 100%;
default 50%.
KP
Admin
Sets the Proportional value of the PID control loop. Adjustable 0.1 to 15; default 1.0.
TI
Admin
Sets the Integral value of the PID control loop. Adjustable 0.1 to 200; default 100.
TD
Admin
Sets the Derivative value of the PID control loop. Adjustable 0.0 to 200; default 0.0
Table 15: Navigation
Button
Access level
Description
Home
Service
Returns to the Home screen.
Condenser
Service
Return to the Condenser screen.
39
Model YD Mod D with OptiView Control Center
Содержание YD Mod D
Страница 2: ...2 Model YD Mod D with OptiView Control Center...
Страница 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Страница 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Страница 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Страница 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Страница 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Страница 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Страница 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Страница 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Страница 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Страница 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Страница 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Страница 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Страница 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Страница 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Страница 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Страница 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...