Table 142: Cycling shutdown messages
Message
Description
Control Panel – Power
Failure
A control power failure has occurred. If the power failure occurred while the chiller was
running, it will automatically restart when power is restored. However, if the power failure
duration was < the duration of the coastdown period when power is restored, the remainder
of the coastdown will be performed, prior to the chiller starting. This message can indicate
a cycling (auto-restart after power failure) or safety (manual restart after power failure)
shutdown, depending upon the control center configuration. It indicates a cycling shutdown
when displayed in orange characters; safety shutdown when displayed in red characters.
The control center is configured for auto-restart or manual restart after power failure by a
qualified service technician.
Leaving Chilled Liquid
– Flow Switch Open
The chilled liquid flow switch has remained open for 2 continuous seconds while the
chiller was running or failed to close during the system pre-lube period. The chiller will
automatically restart when the flow switch closes.
Condenser – Flow Switch
Open
The condenser water flow switch has remained open for 30 continuous seconds while the
chiller was running. This check is bypassed for the first 30 seconds of system run. The chiller
will automatically restart when the flow switch closes.
139
Model YD Mod D with OptiView Control Center
Содержание YD Mod D
Страница 2: ...2 Model YD Mod D with OptiView Control Center...
Страница 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Страница 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Страница 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Страница 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Страница 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Страница 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Страница 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Страница 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Страница 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Страница 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Страница 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Страница 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Страница 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Страница 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Страница 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Страница 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...