Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 3 - START SEQUENCE
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
32
of
157
Start Sequence
1.
The Controller’s red
DEMAND
LED status indicator will light.
2. The unit checks all five pre-purge safety switches listed at the beginning of this section. The Edge [i]
Controller
’s ignition sequence screen walks you through the ignition screens and demonstrates (or
highlights) which switches are not met. SSOV locations are shown in Figure 3-1a through 3-1d.
Figure 3-1a: BMK750 & 1000 SSOV Location (P/N 22322 shown)
Figure 3-1b: BMK1500 & 2000 SSOV Location (P/N 22314 shown)
TO
AIR/FUEL
VALVE
MANUAL
SHUT-OFF
VALVE
LOW GAS
PRESSURE
SWITCH
HIGH GAS
PRESSURE
SWITCH
SSOV
SSOV
TO AIR/FUEL
VALVE
MANUAL
SHUT-OFF VALVE
NATURAL
GAS INLET
NATURAL
GAS INLET
LOW GAS
PRESSURE
SWITCH