Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 7
– BOILER SEQUENCING TECHNOLOGY
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
108
of
157
OPTION 1
Instructions: Constant Setpoint with Direct Wired Header Temp Sensor
2. Go to:
Main Menu
→
Advanced Setup
→
BST Cascade
→
Application Configuration:
•
Set the
Unit Address
parameter to the communication address of the unit.
On the BST Manager only:
1. Go to
Main Menu
→
Advanced Setup
→
BST Cascade
, set the Parameters to the Values
in each menu listed in the table below.
Menu/Screen Name
Parameters
Values
Cascade
Configuration
Auto Manager Transfer
Disabled (This option is available on the
Manger unit only)
Unit Mode
BST Manager
Hdr Temp Sensor
FFWD Temp
Application
Configuration
Application
Space Heating
SH Operating Mode
Constant Setpoint
SH Setpoint
Header temperature required for the cascade
Cascade Comm
Min address
The
minimum
unit address in the cascade
Max address
The
maximum
unit address in the cascade
Cascade Baud Rate
The baud rate for the cascade.