Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 7
– BOILER SEQUENCING TECHNOLOGY
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
112
of
157
OPTION 3
Instructions: Outdoor Reset, Direct Wired Header Temp Sensor & Outdoor Sensor
Step 3
– OPTION 3 CONFIGURATION
On All Boiler:
1. Go to:
Main Menu
→
Advanced Setup
→
BST Cascade
→
Cascade Configuration
:
•
Set the
Unit Mode
parameter to
BST Client
.
2. Go to:
Main Menu
→
Advanced Setup
→
BST Cascade
→
Application Configuration
:
•
Set the
Unit Address
parameter to the communication address of the unit.
On the BST Manager only:
1. Go to
Main Menu
→
Advanced Setup
→
BST Cascade
, set the Parameters to the Values
in each menu in the table below.
Menu/Screen Name
Parameters
Values
Cascade
Configuration
Auto Manager
Transfer
Disabled (This option is available on the
Manager unit only)
Unit Mode
BST Manager
Hdr Temp Sensor
FFWD Temp
Application
Configuration
Application
Space Heating
SH Operating Mode
Outdoor Reset
Outdoor Temp Sensor
Direct
Plant Setpoint
Header temperature required for the cascade
Cascade Comm
Min address
The
minimum
unit address in the cascade
Max address
The
maximum
unit address in the cascade
Cascade Baud Rate
The baud rate for the cascade.