Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 2: OPERATION
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
22
of
157
Unit Application
Select
Select unit’s application:
SH
,
DHW
or
Other
.
Unit SH Operating Mode
Unit DHW Operating Mode
Unit Other Operating Mode
Toggle
Choose either
Constant
or
Remote Setpoint
.
Unit SH Setpoint
Unit DHW Setpoint
Unit Other Setpoint
Numeric Entry
Sets the unit’s setpoint (
Unit Operating Mode = Constant
Setpoint
).
Analog Input Source
Select
Choose:
Spare Analog In 1
,
Spare Analog In 2
,
Spare
Analog In 3
(
Unit Application
=
DHW
or
Other
and
Unit
Operating Mode
=
Remote Setpt
).
Name
Select
Choose:
Not Assigned
,
Remote Setpt 2
,
Swing V1 Fdbk
,
Swing V2 Fdbk
,
Blr VSP Fdbk
,
DHW VSP Fdbk
,
SmartPlate
VP
,
NOx
(
Unit Application
=
DHW
or
Other
and
Unit
Operating Mode
=
Remote Setpt
).
Remote Signal
Select
Select the source of the remote signal:
4-20mA
,
0-20mA
,
BST
(PWM) Input
,
Network
,
1-5V
,
0-5V
,
BAS
(
Unit SH
Operating Mode
=
Remote Setpoint
,
Combination
or
Direct
Drive
).
Unit DHW Remote Signal
Unit Other Remote Signal
Select
Select the source of the of the remote signal: (
Unit DHW
Operating Mode
or
Unit Other Operating Mode
=
Remote
Setpoint
.
Unit Address
Toggle
Specifies the unit’s Modbus address (
Remote Signal =
Network
).
Cascade Baud Rate
Numeric Entry
Specifies Modbus baud rate (
Remote Signal = Network
).
Outdoor Air Temp Sens
Numeric Entry
Choose how to communicate with the outdoor temp sensor:
Off
,
BAS
,
Direct
or
Network
(
Unit Application
=
SH
and
Unit SH Operating Mode
=
Outdoor Reset
).
OAR Min Outside Temp
Numeric Entry
The minimum outside air temperature the system will read
(
Unit Application
=
SH
and
Unit SH Operating Mode
=
Outdoor Reset
).
OAR Max Setpoint
Numeric Entry
The
maximum
allowable setpoint (
Unit Application
=
SH
and
Unit SH Operating Mode
=
Outdoor Reset
).
OAR Max Outside Temp
Numeric Entry
The maximum Outside Temperature that the system will
operate to (
Unit Application
=
SH
and
Unit SH Operating
Mode
=
Outdoor Reset
).
OAR Min Setpoint
Numeric Entry
The
minimum
allowable setpoint (
Unit Application
=
SH
and
Unit SH Operating Mode
=
Outdoor Reset
).
Outdoor Rst Setpt
Numeric Entry
The current outdoor reset setpoint, based on the four OAR
parameters (
Unit Application
=
SH
and
Unit SH Operating
Mode
=
Outdoor Reset
).
Main Menu
→
Advanced Setup
→
Unit
→
Maintenance
12 Month Maintenance
Complete?
Yes/No
Specifies 12 Month Maintenance completed.
Fire Side Inspection
Yes/No
Specifies Fire Side Inspection completed.
Optical Burner Inspection
Yes/No
Specifies Optical Burner Inspection completed
Water Side Inspection
Yes/No
Specifies Water Side Inspection completed.
CSD-1 Safety Device
Inspection
Yes/No
Specifies CSD-1 Safety Device inspection completed.
Combustion Calibration
Check
Yes/No
Specifies Combustion Calibration Check completed.
2.3.4.2
Main Menu
→
Advanced Setup
→
BST Cascade
Main Menu
→
Advanced Setup
→
BST Cascade
→
Cascade Configuration
Parameter Name
Type
BST Client
BST Manager
Description
Unit Mode
Select
Client/Manager
Specify Unit Mode:
Off
,
BST
Client
or
BST
Manager
.
BST Outdoor Temp
Read Only
Client/Manager
The current reading of the outdoor temperature
sensor (
Outdoor Air Temp Sens
=
Network
,
Direct
or
BAS
).