Kerosene Conversion Instructions for
Vitorondens 200-T 33kW, 40kW and 50kW

n

  Isolate power supply and oil supply lines.

n

  Set the burner into the servicing position as per boiler service  

 manual. 

 

  

n

  Clean strainer, filter, fuel lines, and tank and remove water.

n

  If the appliance is 40kW or 50kW Remove burner flame tube.

n

  Loosen the 3 nuts securing the burner to the boiler door and  

  carefully withdraw the burner from the boiler. 
  

Содержание Vitorondens 200-T Series

Страница 1: ...y lines n Set the burner into the servicing position as per boiler service manual n Clean strainer filter fuel lines and tank and remove water n If the appliance is 40kW or 50kW Remove burner flame tube n Loosen the 3 nuts securing the burner to the boiler door and carefully withdraw the burner from the boiler ...

Страница 2: ...itorondens 200 T 33kW 40kW and 50kW n Remove the 3 socket head bolts securing the mixing assembly cover to the front of the burner housing and slide the cover off the mixing assembly Figure 1 40kW and 50kW appliance Figure 2 33kW appliance ...

Страница 3: ... 40kW and 50kW appliance Figure 4 33kW appliance n Carefully disconnect the electrical connection plug from the oil pre heater and then plug the link wire supplied into the pre heater cable plug between the brown and black wires n Fasten the cable tie supplied in the conversion kit around the end of the electrical supply cable approximately 3 mm from the end of the outer insulation Cut off the exc...

Страница 4: ...ions n Check electrode position and electrode spark gap n Recommission the burner as per the servicing instructions using the new pump pressures combustion chamber pressure and initial air setting shown in Kerosene parameter table below Appliance 33kW 40kW 50kW Nozzle 0 85 80 S 1 1 80 S 1 35 80 S Danfoss part No 030F8918 030F8922 030F8926 Pump Pressure bar PSI 9 131 8 116 9 131 Chamber pressure 11...

Отзывы: