Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 2: OPERATION
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
26
of
157
Lag Unit
Numeric Entry
Specify the address of the Lag unit (0 to 16,
Lead/Lag Setting
=
Select Lead Lag
).
2.3.4.3
Main Menu
→
Advanced Setup
→
Com & Failsafe
Main Menu
→
Advanced Setup
→
Comm & Network
→
onAER
onAER Mode
Select
To enable onAER, select the communication method:
Ethernet
,
Wi-Fi
or
Wiznet
(for units where the Edge
Controller replaced a C-More).
Unit Upload Time
Numeric Entry
Determines how frequently unit data is uploaded to the
server (30 to 9999 sec.).
Cascade Upload Time
Numeric Entry
Determines how cascade data is uploaded to the server
(60 to 9999 sec.).
Status
Read Only
The communication interface status.
Main Menu
→
Advanced Setup
→
Comm & Network
→
Ethernet
DHCP
Enable/Disable
Enables/disables
DHCP (Dynamic Host Configuration
Protocol).
IP Address
Numeric Entry
The static IP address of the unit
(
DHCP
=
Disabled
).
Subnet
Numeric Entry
The subnet address of the network
(
DHCP
=
Disabled
).
Gateway
Numeric Entry
The IP address of the Gateway
(
DHCP
=
Disabled
).
DNS1
Numeric Entry
The IP address of
DNS Server 1
(
DHCP
=
Disabled
).
DNS2
Numeric Entry
The IP address of
DNS Server 2
(DHCP
=
Disabled
).
ICMP PING
Enable/Disable
Allows the unit to be pinged..
Main Menu
→
Advanced Setup
→
Comm & Network
→
Communication Failsafe
Unit Failsafe Mode
Toggle
Choose how the unit will operate when either the Manager
communication or a Remote Signal is lost:
Constant Setpt
or
Shutdown
.
Unit Failsafe Setpoint
Numeric Entry
The unit’s default setpoint when communication fails
(60 to
160°F,
Unit Failsafe Mode
=
Constant Setpt
).
2.3.4.4
Main Menu
→
Advanced Setup
→
Ancillary Devices
Main Menu
→
Advanced Setup
→
Ancillary Device
→
Interlocks
Remote Interlock Name
Select
Choose the Remote Interlock:
Flow
,
Damper
,
Louver
,
Other
.
Remote Interlock Use
Toggle
Specify what will shut down if the selected Remote
Interlock is open:
Unit Shutdown
or
Sys Shutdown
.
Delayed Interlock Name
Select
Choose the Delayed Interlock:
Valve 1
,
Valve 2
,
Louver 1
or
Louver 2
.
Auxiliary Delay
Numeric Entry
Select the Delayed Interlock
’s delay
(0 to 240 sec.).
2.3.4.5
Main Menu
→
Advanced Setup
→
Performance
Main Menu
→
Advanced Setup
→
Performance
→
Temperature Control
Main Menu
→
Advanced Setup
→
Performance
→
Temperature Control
→
PID Setting
Proportional Band
Numeric Entry
Generates a fire rate based on the error that exists
between the setpoint and the actual outlet temperature. If
the error is less than Proportional Band, fire rate will be
less than 100%. If the error is equal to or greater than
proportional band, the fire rate will = 100% (1°F to 120°F).
Integral Band
Numeric Entry
Specifies the fraction of the output, due to setpoint error, to
add or subtract from the output each minute to move
towards the setpoint. (0.00 to 5.00)