Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 6
– MODES OF OPERATION
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
103
of
157
Combination Control System Setup Instructions
1. As a prerequisite, verify that the unit is
not
a BST Client or Manager. Go to:
Main Menu
→
Advanced Setup
→
BST Cascade
→
Cascade Configuration
, Unit Mode
=
Off
.
2. On the Controller, go to:
Main Menu
→
Advanced Setup
→
Unit
→
Application
Configuration
.
3. Press
SH Operating Mode
and choose
Combination
.
4. Press the
Remote Signal
parameter and choose
Network
.
While it is possible to change other temperature-related functions for
Combination
mode, these
functions are preset at the factory. These default settings work well in most applications. It is
suggested that AERCO be contacted prior to changing settings other than the unit’s setpoint.