Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 7
– BOILER SEQUENCING TECHNOLOGY
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
110
of
157
OPTION 2
Instructions: Constant Setpoint with Modbus Wired Header Temp Sensor
On the BST Manager only:
1. Go to
Main Menu
→
Advanced Setup
→
BST Cascade,
set the Parameters to the Values
in each menu in the table below.
Menu/Screen Name
Parameters
Values
Cascade
Configuration
Auto Manager Transfer
Enabled (This is available on the Manager
unit only)
Auto failover Type
C-More
Backup Manager Address Enter the designated backup unit address
Unit Mode
BST Manager
Hdr Temp Sensor
Network
Sensor
Comm Address
240
Hdr Temp Point
14
Application
Configuration
Application
Space Heating
SH Operating Mode
Constant Setpoint
Plant Setpoint
Header temperature required for the cascade
Cascade Comm
Min address
The
minimum
unit address in the cascade
Max address
The
maximum
unit address in the cascade
Cascade Baud Rate
The baud rate for the cascade.