Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 8
– MAINTENANCE
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
140
of
157
Benchmark 5000/6000
Long Term Blower Storage Instructions
Example Storage / Maintenance Schedule Log
Item
Action
Dates Checked
1
Re-inspect units to insure any protective devices
used are functioning properly. Check for scratches
in the finish which will allow corrosion or rust to
form
2
Rotate wheel a minimum of 10 full revolutions to
keep the motor bearing grease from separating
and drying out.
(THIS STEP IS CRITICAL!)
5.
General Motor Procedure:
If the motor is not put into service immediately, the motor must be stored in a clean, dry,
warm location. Minimum temperature of 50°F. (10°C,). Several precautionary steps must be
performed to avoid motor damage during storage.
a)
Use a “Megger” each month to ensure that integrity of the winding insulation has been
maintained. Record the Megger readings. Immediately investigate any significant drop
in insulation resistance.
b) DO NOT lubricate the motor bearings during storage. Motor bearings are packed with
grease at the factory.
c) If the storage location is damp or humid, the motor windings must be protected from
moisture. This can be done by applying power to the motor’s space heaters, (IF
AVAILABLE) while the motor is in storage. If the motor does not have space heaters,
storing it in a damp or humid location will, very quickly, cause internal corrosion and
motor failure which is not warranted.
NOTE:
For specific storage instructions, for the actual motor and any accessory
parts that were supplied, refer to the manufacturer’s instructions.
Figure 8-11: Benchmark 5000-6000 Blower Exploded View
1. INLET FLANGE
2. INLET-SIDE PLATE
3. INLET-SIDE HOUSING
4. BLOWER WHEEL
5. DRIVE-SIDE HOUSING
6. DRIVE-SIDE PLATE
7. BASE, FAN
8. MOTOR
9. RISER BLOCKS *
10. RISER BASE *
* IF REQUIRED