Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 5
– SAFETY DEVICE TESTING
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
83
of
157
HIGH Gas Pressure Test Instructions: BMK3000
– 6000 ONLY
Figure 5-4c: High Gas Pressure Switch Locations & Test Ports
– BMK6000
Shown
DOWNSTREAM
SSOV WITH POC
SWITCH
NATURAL GAS
HIGH Gas
Pressure Port
Install manometer here for
High
Gas Pressure
test
PROPANE Gas Pressure Port
Install manometer here for
High Gas Pressure
test
Alternative location for manometer
if hose barb is preferred
PROPANE
HIGH GAS
PRESSURE SWITCH
- BMK6000
–
10.5” W.C., 2.6 kPa
- BMK5000
–
4.5” W.C., 1.1 kPa
NATURAL GAS HIGH GAS
PRESSURE SWITCH
- BMK6000
–
10.5” W.C., 2.6 kPa
- BMK5000
–
11.0” W.C., 2.7 kPa