Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 2: OPERATION
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
29
of
157
Off Delay
Numeric Entry
Defines a Shutoff delay, during which time the unit remains
at minimum fire rate after the unit has sequenced to
shutoff. It is activated only when
Off Delay Threshold
is
reached (0 to 9999 secs). (
Slow Shutdown
=
Enabled
).
Off Delay Threshold
Numeric Entry
The Fire rate that activates the
Off Delay
function
(40 to 100 %). (
Slow Shutdown
=
Enabled
).
Shutoff Delay Temp
Numeric Entry
Specifies the number of degrees above setpoint that the
outlet temperature can rise without triggering a unit shut
down (0 to 25°F).
Demand Offset
Numeric Entry
The temperature offset from setpoint before a unit may
come online. (0°F to 25°F). This can reduce excessive
cycling in
AUTO
mode. When above 0, the unit will not turn
on again until
Valve Position In
reaches the
Start Level
value
AND
the outlet temperature goes below
Demand
Offset;
the unit will fire at the ignition valve position or
below for 1 minute. If this entry equals 0, the unit will turn
on when the
Valve Position In
=
Start Level
.