Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 4
– INITIAL START-UP
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
64
of
157
NOTE:
These instructions assume that the
inlet air temperature is between 50°F and 100°F (10°C
– 37.8°C)
. If NOx readings exceed the target values in Table 4-4, above, or Table 4-6, below,
increase the O
2
level up to 1% higher than the Target value. You must then record the
increased O
2
value on the Combustion Calibration sheet.
22. On Benchmark 3000 - 6000 units
only
, record the manifold (downstream) gas pressure at
100%. This value will be used in Section 5.2.2:
Low Pressure Gas Test
, and Section 5.3.2:
High Pressure Gas Test
.
23. Once the O
2
level is within the specified range at 100%:
•
Enter the
Flame Strength
,
NOx
and
CO
readings from the Combustion Analyzer
and multi-
meter in the Manual Combustion Calibration screen’s
Reading
column.
•
Enter the same values, plus the
O
2
value, on the Combustion Calibration Data Sheet
provided with the unit.
24. Lower the Valve Position to the next calibration point using the
(Left) arrow key (if using
Method 1 in step 11) or the Fine Valve Position
– (Minus) key (if using Method 2).
•
BMK750P & 1000P:
80%
•
BMK1500/2000/2500 DF & P:
70%
•
BMK3000 DF & P:
85%
•
BMK5000P & 6000P:
70%
•
BMK5000DF & 6000DF:
85%
25. Repeat step 17, 18 and 21 at that valve position and the rest of the valve positions in Table
Table 4-6a and 4-6b, depending on model. The O
2
, NOx and CO should stay within the
ranges shown in these tables.
TABLE 4-6a: PROPANE Final Valve Positions: BMK750
–
3000
Valve Position
Oxygen (O
2
) %
Nitrogen oxide (NOx)
Carbon Monoxide (CO)
BMK750/1000
80%
5.5% ± 0.2%
<100 ppm
<150 ppm
60%
5.5% ± 0.2%
<100 ppm
<150 ppm
45%
5.5% ± 0.2%
<100 ppm
<150 ppm
30%
6.3% ± 0.2%
<100 ppm
<100 ppm
18%
5.5% ± 0.2%
<100 ppm
<100 ppm
BMK1500
70%
5.2% ± 0.2%
<100 ppm
<150 ppm
50%
5.3% ± 0.2%
<100 ppm
<150 ppm
40%
6.2% ± 0.2%
<100 ppm
<150 ppm
30%
7.0% ± 0.2%
<100 ppm
<100 ppm
18%
8.5% ± 0.2%
<100 ppm
<100 ppm
BMK2000
70%
6.5% ± 0.2%
<100 ppm
<150 ppm
50%
6.5% ± 0.2%
<100 ppm
<150 ppm
40%
6.5% ± 0.2%
<100 ppm
<150 ppm
30%
6.5% ± 0.2%
<100 ppm
<100 ppm
18%
5.5% ± 0.2%
<100 ppm
<100 ppm