Catalog No.: 2000.203E
Effective: 12-1-07
Replaces: 4-1-05
Job:
Engineer:
Contractor:
Prepared By:
Date:
Model:
Indoor
LOW NOx
Less than 40 nanograms per joule
EFFICIENT
82% efficiency – highest of any atmospheric boiler
available today
THERMAL SHOCK PROOF
Twenty-year warranty against thermal shock damage
up to 150°F differential
Maximum operating temperature: 230°F
LIGHTWEIGHT
A floor load of 70 lbs./sq. ft. or less
HIGH RECOVERY
Cuts fuel costs substantially because the standby and
radiation losses normal to other boilers and
tank-type water heaters are eliminated
LOW WATER OPERATING TEMPERATURE
Operates with water temperature as low as
105°F without condensing
Heat Exchanger
ASME Inspected and Stamped
160 PSIG
National Board Approved
Headers
Cast Iron Glass-lined – Standard
Bronze – Option A-1
Finned
Tubing
Copper – Standard
Cupro Nickel – Option A-3
ASME Steel Tube Sheet
Silicone
O-Rings
ASME Pressure Relief Valve
45 PSIG – Standard
PSIG ASME – Optional
Temperature and Pressure Gauge,
Shipped Loose
Water
Connections
Left Hand – Standard
Right Hand – Option A-6
Flow Configuration – Two-pass
Pump – Optional
Mounted, 1/8 HP
,
120 V, 1
∅
,
60 Hz
Controls
120V, 60Hz, 1 Ph Power Supply
120/24V
Transformer
100% Pilot Shut-off/Lockout
Electronic,
Intermittent Ignition (IID) Pilot
Controls (cont'd)
High Limit Control, Manual Reset
On/Off
Switch
Flow
Switch
Economaster II Pump Time Delay
Gas Train
Natural
Gas
Manual Main Gas Shut-off Cock
Main Gas Pressure Regulator
Redundant Safety Shut-off Valve
Control Valve
Firing
Mode
On/off (H4)
Two-stage firing (H3)
Design
Certified
ANSI Z21.13 H Stamp
Construction
Front
Controls
Stainless Steel, Fan-Assisted
Burners
Polytuf Powder Coat Finish
Draft
Diverter
Base – Optional
Combustible Floor Shield –
Option J-1
Temperature Controls
B-6
2-stage Aquastat –
100-200ºF
B-26 2-stage Digital Controller
B-27 2-stage Digital Controller,
Outdoor Reset
Y-241 Electronic Sequencer,
1-4 Stages
Y-281 Electronic Sequencer,
1-8 Stages
Additional Safety Controls
F-10 Low Water Cut-off Probe
I-1
High Limit Control, Auto
Reset
S-1
Low Gas Pressure Switch
S-2
High Gas Pressure Switch
Regulatory Agency Requirements
Raytherm
®
- Type H
Hydronic Heating Boilers
Models 181-401 - Indoor
Low NOx