114 Commissioning
WAGO-I/O-SYSTEM 750
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Behavior of the PROFIsafe I/O module in the event of a failure
If an error is detected on a digital input or digital power output by the PROFIsafe
I/O module, the entire PROFIsafe I/O module is passivated by the process image
of all digital inputs being set to "0" and all digital power outputs being switched
off.
For detailed information, read the section "Diagnostics".
Use the same value for the output tolerance time of output O1 and O2!
If the
Output Configuration
parameter is set to "H-Side/L-Side 1" or "H-Side/H-
Side 1", the values of the
Output tolerance time
parameter for both outputs O1
and O2 must be set to the same value. This is checked by the PROFIsafe I/O
module during the parameterization procedure and a suggested correction is
indicated by the PROFIsafe I/O module in the WAGO parameterization tool in
case of deviation.
Use the same value for the test pulse duration of output O1 and O2!
If the
Output Configuration
parameter is set to "H-Side/L-Side 1", the values of
the
Test pulse duration
for both outputs O1 and O2 must be set to the same
value. This is checked by the PROFIsafe I/O module during the parameterization
procedure and a suggested correction is indicated by the PROFIsafe I/O module in
the WAGO parameterization tool in case of deviation.
The value of the output tolerance time must not be less that the value of the
test pulse duration!
The value of the
Output tolerance time
parameter may not be less than the value
of the
Test pulse duration
parameter. This is checked by the PROFIsafe I/O
module during the parameterization procedure and a suggested correction is
indicated by the PROFIsafe I/O module in the WAGO parameterization tool in
case of deviation.