Table 16: Technical data, digital power outputs
Power outputs
O1 … O2
2 outputs for actuators
Achievable safety classes
2 x Cat. 2/PL d acc. EN ISO 13849-1,
1 x Cat. 4/PL e acc. EN ISO 13849-1,
2 x SIL2 acc. EN 62061,
1 x SIL3 acc. EN 62061,
2 x SIL2 acc. IEC 61508,
1 x SIL3 acc. IEC 61508
Output nominal
current
O1
10 A
O2
10 A
Output residual current at signal "0"
< 1 mA
Output protection
O1 … O2
Short circuit and overload by external
fuse
(see section "Power Supply
Requirements")
Limitation of the inductive transient
voltage
See section "Switching Inductive
Loads"
Response threshold
line break detection
Min.
66 μA
Max.
130 μA
Parallel connection of outputs
Not possiblee
Drive of an EN61131-2 compatible input See section "Connecting the Digital
Power Output to Digital Inputs"
Response Times
See section "Response Times"
Switchting frequency
max.
Resistive load
50 Hz
Capacitive load
50 Hz (at 100 nF capacitive load)
Inductive load
DC13 (50W) acc.
to
IEC 60947-5-1
0.1 Hz (see section "Switching
Inductive Loads")
Capacitive Last per output C
L max.
10000 µF (see section "Switching
Capacitive Loads")
Line length
max.
unshielded
200 m
shielded
200 m
Test pulse duration
Configurable between 0 ms and 500 ms
in steps
(see section "Parameterization" > "Test
Pulse Duration Parameters")
Output tolerance time
Configurable between 2 ms and 500
ms, in steps
(see section "Parameterization" >
"Output Tolerance Parameters")
Response thresholds of the output and
external voltage monitoring
Dependent on the output configuration
(see section "Connection Examples for
Digital Power Outputs")