112 Commissioning
WAGO-I/O-SYSTEM 750
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Read the section "Connection Examples for Digital Power Outputs" > output
configuration "H-Side/L-Side 2". Please also note the safety information.
7.4.5.8.3 Output Configuration H-Side/H-Side 1
If you have set the
Output Configuration
parameter to the value "H-Side/H-
Side 1", then the PROFIsafe I/O module switches the 24V potential of the field
supply voltage exclusively. In this case, the load is switched by internal serial
redundancy two-channel and separated exclusively from the 24V potential of the
field supply voltage. Connect connection O1B to connection O2A. Connect the
load from connection O2B to the 0V potential of the field supply voltage.
Figure 48: Output configuration H-Side/H-Side 1
Read the section "Connection Examples for Digital Power Outputs" > output
configuration "H-Side/H-Side 1".
7.4.5.8.4 Output Configuration H-Side/H-Side 2
If you have set the
Output Configuration
parameter to the value "H-Side/L-
Side 2", then you can use the PROFIsafe I/O module to switch two loads each
with full rated current. The loads are connected between connection O1B to the
0V potential and from connection O2B to the 0V potential of the field supply
voltage.
Figure 49: Output configuration H-Side/H-Side 2
Connect connection O2A to the 24V potential of the field supply voltage directly.