150 Appendix
WAGO-I/O-SYSTEM 750
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Table 45: PROFIsafe F parameters
F Parameters
Default value Description
F_Dest_Add
1022
The
F_Dest_Add
parameter specifies the
PROFIsafe destination address of the
PROFIsafe I/O module. For
F_Dest_Add
,
values from 1 to 65534 can be selected.
Each address value may appear in the system
only once. This is checked by the configuration
tool of the safe PLC.
For PROFIsafe communication to begin, the
parameter value must match the PROFIsafe
address of the PROFIsafe I/O module.
F_WD_Time
150
The
F_WD_Time
parameter determines the
monitoring time for PROFIsafe
communication between F controller and
PROFIbus I/O module.
At least one valid PROFIsafe telegram must be
exchanged between the safe PLC and the
PROFIsafe I/O module within the monitoring
time.
If this condition is not met, the safe PLC or
PROFIsafe I/O module initiates a safe state.
The monitoring time must be selected, so that
telegram execution times are tolerated, but an
interruption in the connection is detected
quickly enough.
The monitoring time can be specified in steps
of 1 ms. The possible value range (50 to 10000
ms) is specified by the WAGO device
description file (GSD/GDML).