130 Diagnostics
WAGO-I/O-SYSTEM 750
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Table 41: Diagnostic messages
Alarm
Description
Invalid
iParameters
Diagnostic
type
Module Diagnostics
Coding:
0x0200
LED
indication
Group error (E) red,
parameterization (H) red, 1 Hz flashing
Solution
The individual parameter set for the F I/O
module is inconsistent. Correct the
parameterization taking into account
dependencies between individual settings.
Invalid iParam.
from iPar server
Diagnostic
type
Module Diagnostics
Coding:
0x004B
LED
indication
Group error (E) red,
parameterization (H) red, 1 Hz flashing
Solution
The individual parameter set for the F I/O
module provided by the iPar server are
inconsistent. Make sure that a valid
iParameter set exists on the iPar server.
Check fieldbus transmission if necessary.
Invalid F_CRC1
Diagnostic
type
Module Diagnostics
Coding:
0x0047
LED
indication
Group error (E) red
PROFIsafe (G) red
Solution
The F_CRC1 form from the F parameter
set is invalid. Create a consistent F
parameter set.
Invalid
F_Dest_Add
Diagnostic
type
Module Diagnostics
Coding:
0x0041
LED
indication
Group error (E) red
Solution
The PROFIsafe address of the F I/O
module must lie within the range of 1 to
65534. Correct the F parameterization.
Invalid
F_Source_Add
Diagnostic
type
Module Diagnostics
Coding:
0x0042
LED
indication
Group error (E) red
PROFIsafe (G) red
Solution
The PROFIsafe address of the F host must
lie within the range of 1 to 65534. Correct
the F parameterization.