WAGO-I/O-SYSTEM 750
Commissioning
93
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
7.3
Setting the PROFIsafe Address using the Coding
Switch
Disconnect the power from the node before making the settings!
Switch off the fieldbus node before you pull the PROFIsafe I/O module out of the
fieldbus node to change the settings!
Use only appropriate tools to change the settings!
To set the switching elements of the coding switch, use only suitable objects (e.g.,
test prod or watchmakers screwdriver). Never exert pressure on the switching
elements.
Coding switch is inaccessible when the I/O module is plugged in!
To set the PROFIsafe address on the coding switch, the I/O module must be
pulled out of the fieldbus node.
Use the switching elements of the coding switch to set the PROFIsafe address to a
value from 1 to 1023.
7.3.1
Setting the PROFIsafe Address using the WAGO
Parameterization Tool
Effectiveness using the WAGO Parameterization Tool
The PROFIsafe address set using the WAGO parameterization tool only takes
effect when the address set on the coding switch of the I/O module equals 0.
To configure the PROFIsafe address through storage in the parameter data set of
the I/O module, set the PROFIsafe address in the WAGO parameterization tool to
the required value and save the current parameter data set to the I/O module.
Configuring the PROFIsafe I/O module is described in the section
"Parameterization with the WAGO Parameterization Tool".