WAGO-I/O-SYSTEM 750
Connect Devices
83
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Line break detection not possible!
When connecting a digital input to digital power output O2B, line break detection
is not possible.
Set the
Line break detection
parameter to "inactive" because otherwise the
PROFIsafe I/O module is passivated and the "Line break" diagnostic message is
output.
Line break detection is not safety related and cannot be part of the safety function
under any circumstances.
Note about the Short circuit test parameter
If you connect digital power output O2B to a digital input, you have to set the
Short circuit test
parameter to "inactive". Otherwise, the PROFIsafe I/O module
is passivated and the "Short circuit" diagnostic message is output.